The completely pre-assembled pump groups for the mixed heating circuit are equipped with high-efficiency pumps with an overall length of 180 mm, including a power supply cable, ball valves on the heating flow and return flow side with a thermometer handle (with a 20 mbar backflow preventer valve in the return) and a mixing valve with bypass, temperature sensor and a controlled mixer actuator.
| Nominal diameter | DN 25 |
| Connection dimensions | thermo-tap side top – 1 1/2“ G flat sealing bottom – 1 ¼“ Rp |
| Center distance heating flow and return flow | 125 mm |
| Dimensions (H x W x L) | 400 mm x 250 mm x 200 mm |
| Materials | EPP, brass, steel, EPDM seals |
| Field of application | Kvs 6 m3/h, 35 kW, mixer motor 20 °C – 80 °C |
| Operating pressure | max. 6 bar |
| Nominal diameter | DN 32 |
| Connection dimensions | thermo-tap side top – 2“ G flat sealing bottom – 1 ¼“ Rp |
| Center distance heating flow and return flow | 125 mm |
| Dimensions (H x W x L) | 400 mm x 250 mm x 200 mm |
| Materials | EPP, brass, steel, EPDM seals |
| Field of application | Kvs 13.0m3/h, 90 kW, up to 110 °C (depending on pump) |
| Operating pressure | max. 6 bar |